- Gas leak detection at single point
-
Combination with Hot wire semiconductor method detector head enables gas leak detection for low concentration gas
SPECIFICATIONSModel
|
FA-480
|
Measuring Gas
|
Combustible gas in the air
|
Hydrogen in the air
|
Methane in the air
|
Organic solvent in the air
|
Detection Principle
|
Catalytic combustion method (Note 1)
|
Hot wire semiconductor method (Note 2)
|
Hot wire semiconductor method
|
Hot wire semiconductor method
|
Measuring Range
|
0 - 100%LEL
|
0 - 2,000ppm
|
0 - 5,000ppm
|
0 - 500ppm
|
Accuracy
|
Within ±25% of the setting value
|
Within ±25% of the setting value (within a range of 1000ppm from 200ppm)
|
Within ±25% of the setting value (within a range of 1000ppm from 500ppm)
|
Within ±25% of the setting value (within a range of 200ppm from 50ppm)
|
Display Method
|
3-digit LED digital
|
Alarm Method
|
Red LED lights intermittently and buzzer sounds intermittently
|
Alarm Setting
|
Adjustable (Standard;25%LEL, 200ppm, 500ppm, 50ppm)
|
Failure display
|
Red LED lights intermittently and buzzer sounds intermittently
|
Power Source
|
AC100V±10V, 50/60Hz (AC220V as extra option)
|
Alarm contact output
|
1a or 1b contact, AC125V, 0.6A (Resistance load)
|
Analog output
|
4 - 20mA (linear)
|
Detection Point
|
1 point
|
Operating Temperature Range
|
Temperature: -10 - 40℃, Humidity: up to 95%RH
|
Installation
|
Wall mount type (Panel mount type is optional)
|
Dimensions
|
120(W) x 205(H) x 69(D)mm
|
Weight
|
0.9kg
| RD SPECIFICATIONS
Model
|
RD
|
Sampling
|
Diffusion method
|
Measuring Gas
|
Isobutane, IPA (Isopropyl alcohol), Ethylene, Propane, Methane
|
Detection Principle
|
Catalytic combustion method
|
Explosion proof
|
d2G4
|
Dimensions
|
100(W)×140(H)×78(D)mm
|
Weight
|
0.9kg
|
Conformity Detector Alarm Unit
|
FA-470 (discontinued), FA-480, FA-490, KA-700RF, KU-7R/F
|
|
|